Productdetails
Betaling en verzendvoorwaarden
Min. bestelaantal: 1000
Betalingscondities: T/T,L/C
|
Performance Item
|
Technical Value
|
Unit
|
|---|---|---|
|
System Rated Voltage
|
0.6/1
|
kV
|
|
Power Frequency Withstand Test Voltage
|
4/50
|
kV/Hz
|
|
Minimum Ambient Installation Temperature
|
-5
|
°C
|
|
Applicable Working Temperature Range
|
-30 ~ +90
|
°C
|
|
Maximum Continuous Conductor Operating Temperature
|
90
|
°C
|
|
5-Second Short Circuit Resistant Temperature
|
250
|
°C
|
|
Minimum Allowable Bending Radius
|
20 × Overall Cable Outer Diameter
|
mm
|
|
Complete Cable Model
|
AAC/XLPE+AAC/XLPE+AAAC 2×4+4AWG
|
|
Phase Conductor Material Grade
|
1350-H19 All Aluminum Conductor (AAC)
|
|
Phase Conductor Specification
|
4 AWG, 19 Strands Compact Stranding
|
|
Insulation Material Type
|
UV-Stabilized Cross-Linked Polyethylene (XLPE)
|
|
Phase Insulation Thickness
|
60 mils
|
|
Neutral Messenger Material
|
All Aluminum Alloy Conductor (AAAC)
|
|
Neutral Messenger Specification
|
4 AWG, 7 Strands Standard Stranding
|
|
Neutral Wire Breaking Tensile Strength
|
1680 Lbs
|
|
Cable Unit Weight
|
295 Lbs/1000 ft
|
|
Standard Sustainable Ampacity
|
155 Amps
|
![]()
![]()
![]()
Why you choose us?